All BurnerLogix
The Fireye BurnerLogixTM System is a microprocessor based burner management control system
designed to provide the proper burner sequencing, ignition and flame monitoring protection onautomatically ignited oil, gas, and combination fuel burners.
Built-in techniques and algorithms allow the BurnerLogix to learn the characteristics of the fuel being burned and set its internal thresholds to optimize detection under all conditions. And when firing conditions change for the worse, the Adaptive IR system reacts properly and safely shuts the burner down.
The BurnerLogix has a smaller footprint than previous offerings with the keypad selectable parameters, most application requirements are easily solved with one programmer module, resulting in less inventory of spare parts. The ‘revert to pilot’ feature can increase a burner’s turndown capability. The new pigtail wiring base can save time and labor at the OEM’s and can make upgrading existing installations easy and quick.
BurnerLogix Subcategories
The FIREYE YZ300 (YZ320) Interlock Annunciator Module provides increased interlock supervision capability of the BurnerLogix System. The Interlock Annunciator Module connects to any YB110 (YB230) or ZB110 (ZB230) BurnerLogix chassis/amplifier […]
The BurnerLogix Z System is designed to provide the proper burner sequencing, ignition and flame monitoring protection on automatically ignited oil, gas, and combination fuel burners. Through the display, the operator programs the desired setp […]
BurnerLogix Components
YP100 Keypad selectable parameters, non‐recycle operation,modulation, open/closed damper proving, 4 second FFRT
YP102 Keypad selectable parameters, non‐recycle operation, modulation, open/closed damper proving, 2 second FFRT
YP113 Keypad selectable parameters, open/closed damper proving, 10 sec low fire start time, non‐recycle operation, fixed TFI times,10 pilot proving, modulation, 1 second FFRT. Required for CE applications.
YP115 Keypad selectable parameters, includes 0 sec purge time, fixed 0 sec low fire start time, non‐recycle operation, fixed TFI times, pilot proving, modulation, open/closed damper proving, 1 second FFRT. Required for CE applications.
YP118 Keypad selectable parameters, non‐recycle operation, modulation, open/closed damper proving, indefinite pilot hold, revert to pilot from auto, 1 second FFRT
YP138 Keypad selectable parameters, non‐recycle operation, modulation, open/closed damper proving, 4 sec FFRT. Powered inputs provide indefinite hold, pilot hold, revert to pilot from auto.
YP183 Keypad selectable parameters, non‐recycle operation, modulation, open/closed damper proving, 4 sec FFRT. Unpowered inputs provide indefinite hold, pilot hold, revert to pilot from auto. Provides purge complete output.
YP200 Keypad selectable parameters, recycle operation, modulation, 4 second FFRT
YP202 Keypad selectable parameters, recycle operation, modulation, 2 second FFRT
YP300 Keypad selectable parameters, recycle operation, low fire start, early spark termination, 4 second FFRT
YP302 Keypad selectable parameters, recycle operation, low fire start, early spark termination, 2 second FFRT
60‐2810‐1 Pigtail wires, 4 foot long, 4″W x 5″H, color coded and labeled. UL Listed.