All PROGRAMMERS FOR USE WITH MEC320 / MEC480 CHASSIS
The Fireye MEP300, MEP304, MEP335 and MEP397 Programmer Modules are used with the Fireye Modular MicroM control. The MEP300 series programmers provide additional enhancements such as early spark termination, pilot proving and interrupted or intermittent pilot operation. These programmers must be used with the MEC320 and MEC480 series chassis. The programmer module incorporates a plugin design for easy installation.
MEP300 Programmer, relight operation on main flame fail, lockout on PTFI and MTFI flame fail, 10 sec PTFI (fixed), 5 sec pilot proving, 5 sec MTFI.
MEP304 Programmer, 5 sec purge, 10 sec PTFI (fixed), 5 sec pilot proving, 10 sec MTFI, interrupted pilot, interrupted ignition, non-recycle on flame fail.
MEP397 Programmer, 15 sec purge, provides interrupted ignition, interrupted pilot, non recycle on flame fail.
MEP437 Programmer, Valve proof of closure, selectable purge, PTFI timing, intermittent or interrupted, recycle / non‐recycle operation, reset by power interruption of manual reset.
MEP696 Programmer, provides selectable PTFI, selectable baud rate, and selectable recycle / non‐recycle operation. For use with MEC320TS chassis only.
MEP697 Programmer Selectable TFI timing, purge timing, post purge, prove open at start, and recycle / non‐recycle on flame fail. Includes 5 sec pilot proving, early spark termination, 10 sec MTFI, and interrupted pilot.