All Burner Controls
Fireye provides a variety of burner control flame safeguard and combustion controls. Our BurnerPRO™, BurnerLogix™, Flame-Monitor™ and MicroM families provide safe and reliable light off of packaged burners used on commercial and industrial boilers as well as direct fired makeup air units and commercial hot water heaters.
Burner Controls Subcategories
The Fireye BurnerLogixTM System is a microprocessor based burner management control system designed to provide the proper burner sequencing, ignition and flame monitoring protection onautomatically ignited oil, gas, and combination fuel burner […]
BurnerPRO Flame Safeguard The BurnerPRO™ provides the proper burner sequencing, ignition and continuous flame monitoring for commercial heating and process equipment firing oil and gas fuels. BurnerPRO Flame Safeguard (BP110UVF/BP230UVF) Contr […]
D-Series 70D40 and 70D41 Burner Control Fireye Series D10, D20 and D30 burner management controls provide ignition and main flame failure protection for automatically ignited oil and gas burners. Plug-in Amplifier Modules permit the selection […]
The Fireye® FLAME-MONITOR™ System is a microprocessor based burner management control system designed to provide the proper burner sequencing, ignition and flame monitoring pro-tection on automatically ignited oil, gas, and combination fuel bu […]
Fireye Flame Scanners provides a variety of UV and IR flame scanners that accurately detect the presence or absence of flame in a combustion chamber and some provide both self-check and non-self check capabilities.
The inTouch Wireless Monitoring System provides continuous monitoring for up to 10 Flame-Monitor, MicroM and/or BurnerLogix flame safeguard controls. The inTouch System provides 4 dry-contact andAC power inputs. In the event of a lockout or co […]
Fireye® Modular M-Series II Flame Safeguard Controls are compact, modular burner management systems. They are designed to provide automatic ignition and continuous flame monitoring for commercial sizes of heating and process burners that use g […]
Designed to provide automatic ignition and continuous flame monitoring, the M4RT1/M4RT24 is meant for commercial-sized heating and process burners that use gaseous fuels. The M4RT1/M4RT24 control incorporates a safety checking circuit that is […]
Burner Controls Components
MEC480 MicroM chassis with local reset; 230 VAC, 50/60 Hz, provides independent relay outputs on terminals 3 and 4. For use with MEP300 and 600 series programmers.
MEP100 Programmer, Relight function, 10 sec PTFI.
MEP101 Programmer, Relight function, allow flame signal until 60 seconds after interlock circuit closes.
MEP102 Programmer, Non‐recycle on flame fail, 5 second PTFI.
MEP103 Programmer, Fixed 10 sec SISP*, 10 sec MTFI, re‐try once on pilot failure, fixed 30 sec post purge. *Spark Igniter Sensing Period
MEP104 Programmer, Non‐recycle on flame fail, 10 second PTFI.
MEP105 Programmer, Non‐recycle on flame fail, lockout on air‐flow open with flame present, 10 second PTFI.
MEP106 Relight operation, 12 sec purge, 10 sec PTFI, reset lockout on line power interruption.
MEP107 5 sec purge, 10 second PTFI, 5 minute delay following flame failure. For natural draft atmospheric gas burners
MEP108 Non‐recycle operation, 0 sec purge, 15 second PTFI, 10 second post purge, no FM Approval.
MEP109 Programmer, Immediate ignition and pilot after limits are closed, 10 sec PTFI (fixed), 10 sec MTFI, intermittent pilot, non‐recycle on flame fail.
MEP100P Programmer, Relight operation, 10 sec PTFI, 15 sec post purge.
MEP130 Programmer, Relight operation, 30 sec PTFI, no agency approvals